1. Show on high-brightness, high-definition, high resolution ratio 10.4" (640*480) TFT color
  liquid crystal display;
2. The system uses high-speed, high-accuracy digital multiplier to measure all parameters s-
  uch as active (reactive) power, voltage, current, frequency, phase etc and calibrates th-
  em through software;
3. This device has no potentiometer, which protects it from error change caused by transpor-
  tation or other factors, and increases stability and reliability of the system greatly;
4. The system adopts the digital absolutely reactive testing technology that is first inven-
  ted in our country. This technology makes testing under reactive research a situation that
  not influenced by voltage and current unbalance, phase angle dissymmetry and frequency ch-
  ange. This technology also increases the reactive accuracy rate up to 0.1% the first time
  in our country.
5. Assure the power accuracy (0.1% or 0.05%) between temperature of -20≧ to +40≧; test ele-
  ctric energy in four quadrants;
6. Able to equipped with 0.2 %5A transformer (including split non-repeat errors, touching er-
  rors, outside magnetic field interference errors, angle errors and so on);
7. Can be attached with 20A, 100A, 500A, 1000A transformer to directly measure low voltage g-
  auging integrative errors and CT rate ratio and angle accuracy with 5A transformer;
8. Voltage switches automatically from 30V to 480V. Current input value is 5A;
9. Wide working electric source is 50~260V. when researches 380v,it will make over voltage p-
  rotection;
10. Identify three-phase three lines 48 kinds errors and three-phase four lines 96 kinds err-
  ors;
11. The hexagonal nomogram of any kind of line connection is able to be used for line check
  training, after showing incorrect identification;
12. Able to measure the 2nd ~21st harmonic wave of three-phase voltage and current, and save
  all harmonic wave¨s data;
13. Able to show three waveforms of voltage and current at the same time;
14. Provide error calibrating function, so that it is convenient to calibrate errors, but it
  needs password;
15. Update software through PC or Modem;
16. Save all testing data of 10000 watt-hour meters, including working parameters, convenien-
  tly for analysis;
17. Able to be attached with <PEC watt-hour meter management system> software to realize a s-
  ituation like that working without paper;
18. Check single-phase, three-phase three lines,three-phase four lines active and reactive i-
  nduction type watt-hours meter and electronic watt-hours meters(able to receive impulse of
  electronic watt-hours meter) automatically or by hand;
19. Able to calibrate voltage, current, power, power factor, phase and frequency of electrot-
  echnical instrument and transmitter by comparison;
20. Notebook style, light and convenient;
21. Stainless steel painting box, firmness and wear well.